1,Application
Primarily used for 120volt overhead service application such as street lighting,outdoor lighting,and temporary service for construction.To be used at voltages of 600 volts phase-to-phase or less and at conductor temperatures not to exceed 75℃ for polyethylene insulated conductors or 90℃ for crosslinked polyethylene(XLPE) insulated conductors.
2,Construction http://www.electriccablechina.com cable.pinson@gmail.com
Code*Word | Phase conductor | Bare Neutral Message | Nominal lay Length |
Weight Per 1000 ft.(lbs.) |
Allo wable Amp acitles | ||||||
Size (A WG) |
Stranding |
Insul Thick(Mils) |
Size (AWG) |
Stranding |
Rated Strength (lbs.) |
inches | XLPE | PE | XLPE | PE | |
AAC Neutral-messenger | |||||||||||
Pekingese | 6 | 1 | 45 | 6 | 7 | 563 | 10.36 | 61 | 61 | 85 | 70 |
Collie | 6 | 7 | 45 | 6 | 7 | 563 | 10.36 | 64 | 64 | 85 | 70 |
Dachshund | 4 | 1 | 45 | 4 | 7 | 881 | 10.36 | 92 | 92 | 115 | 90 |
Spaniel | 4 | 7 | 45 | 4 | 7 | 881 | 10.36 | 96 | 96 | 115 | 90 |
Doberman | 2 | 7 | 45 | 2 | 7 | 1350 | 14.88 | 147 | 147 | 150 | 120 |
Malemute | 1/0 | 9 | 60 | 1/0 | 7 | 1990 | 14.88 | 234 | 234 | 205 | 160 |
*Code words for XLPE insulated products are formed by adding "/XLPE" to the conventional code words above (e.g.-Chihuahua/XLPE)